GATE VALVES
|
| DN |
150 |
300 |
400 |
600 |
900 |
1500 |
2500 |
|
1
1/2" |
130 |
130 |
130 |
130 |
112 |
112 |
73 |
|
2" |
240 |
240 |
240 |
240 |
210 |
210 |
130 |
|
2
1/2" |
380 |
380 |
380 |
380 |
310 |
310 |
230 |
|
3" |
560 |
560 |
560 |
560 |
520 |
475 |
310 |
|
4" |
1000 |
1000 |
1000 |
1000 |
950 |
850 |
520 |
|
5" |
1650 |
1650 |
1650 |
1650 |
1500 |
1400 |
900 |
|
6" |
2400 |
2400 |
2400 |
2400 |
2230 |
1900 |
1300 |
|
7" |
|
|
|
|
|
|
|
|
8" |
4400 |
4400 |
4400 |
4300 |
4000 |
3500 |
2400 |
|
10" |
7100 |
7100 |
7100 |
6800 |
6130 |
5500 |
3750 |
|
12" |
10200 |
10200 |
10200 |
9800 |
9000 |
8000 |
5400 |
|
14" |
13000 |
13000 |
12300 |
11900 |
11000 |
9500 |
|
|
16" |
17000 |
17000 |
16200 |
15900 |
14500 |
12500 |
|
|
18" |
22000 |
21500 |
21500 |
20100 |
18500 |
16000 |
|
|
20" |
27500 |
27000 |
26000 |
25000 |
24000 |
20000 |
|
|
22" |
34300 |
33500 |
32600 |
30700 |
28100 |
24400 |
|
|
24" |
40200 |
39800 |
39500 |
37500 |
34000 |
29500 |
|
|
26" |
49900 |
48800 |
46700 |
43700 |
40000 |
34600 |
|
|
28" |
58300 |
57200 |
54400 |
50900 |
46800 |
40800 |
|
|
30" |
67800 |
66500 |
63000 |
58900 |
53900 |
48000 |
|
|
32" |
75500 |
75500 |
75500 |
75500 |
|
|
|
|
34" |
|
|
|
|
|
|
|
|
36" |
96000 |
96000 |
96000 |
96000 |
|
|
|
|
38" |
|
|
|
|
|
|
|
|
40" |
|
|
|
|
|
|
|
|
42" |
132000 |
132000 |
132000 |
132000 |
|
|
|
|
44" |
|
|
|
|
|
|
|
|
46" |
|
|
|
|
|
|
|
|
48" |
175000 |
175000 |
175000 |
175000 |
|
|
|
|
50" |
|
|
|
|
|
|
|
|
52" |
|
|
|
|
|
|
|
|
54" |
|
|
|
|
|
|
|
|
56" |
|
|
|
|
|
|
|
|
58" |
|
|
|
|
|
|
|
|
60" |
279000 |
279000 |
279000 |
279000 |
|
|
|
|
62" |
|
|
|
|
|
|
|
|
64" |
|
|
|
|
|
|
|
|
66" |
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOW
COEFFICIENT " cv " DEFINITION:
FLOW RATE in Gallons Per Minute of 60° F Water
with 1.0 Psi Pressure Drop Across Valve.
NOMENCLATURE:
d = Bore Diameter (Inch) (1)
K = Resistance Coefficient
Q = Rate of Flow (Gallons Per Minute)
D P = Pressure Drop (Psi)
r =Weight density Of Fluid (Pounds Per Cubic Ft)
NOTE:
(1) Bore Diameter as Per Asme B16.34
For 32" and Over Bore Diameter
Was Considered as Per Api 6d. |
|
|